Read The Electrical Side Of The Nameplate
Cooling capacity in BTU per hour describes the heat the unit can move. Use the electrical input information to size the supply. Dometic’s Penguin II manual separates compressor rated-load current, locked-rotor current and fan current. It also calls for considering the RV’s other loads when sizing a generator. Record your exact model and use its documentation. A locked-rotor figure alone does not establish how long a particular inverter must carry an overload. Dometic Penguin II unit data (PDF).
Price The Hours You Want To Cool
Suppose your existing energy monitor shows 1,400 W with the compressor and fan on and 100 W with only the fan on. In a four-hour afternoon, the energy at the appliance depends on the weather and how often the compressor runs.
| Four-hour scenario | Calculation | AC energy |
|---|---|---|
| Compressor on half the time | 2 h × 1,400 W + 2 h × 100 W | 3,000 Wh |
| On three quarters of the time | 3 h × 1,400 W + 1 h × 100 W | 4,300 Wh |
At an assumed 90% battery-to-AC efficiency, those cases require about 3,333 and 4,778 Wh from storage before other RV loads or a trip reserve. Use the fan’s actual off-cycle behavior; some systems stop it. If your monitor reports the whole coach, subtract a measured background load or budget the whole-coach total once.
Screen The Candidate Before Counting Solar
Check continuous output for the unit and simultaneous appliances, then confirm motor-start compatibility and allowable duration with the manufacturers. Compare the four-hour requirement with usable battery energy already on board. Add solar to the plan only for the hours and charging power you can reasonably expect at camp. Shading during the hottest hour can change both numbers.