Find The Supply Requirement And The Daily Consumption
Dometic’s DMC4101/DMC4081 manual calls for a DC supply in a specified voltage range capable of at least 15 A. That is a supply requirement. It does not mean the fridge consumes 15 A every minute of the day. An installation’s existing supply and a portable station’s individual DC outlet can have quite different limits. Check compatibility before assuming a direct connection is available. Dometic DMC refrigerator specifications (PDF).
Compare Two Days Of Compressor Time
For a separate illustrative 12 V fridge, assume 60 W while cooling and 2 W while idle. On a mild day with eight running hours, the daily load is (60 × 8) + (2 × 16) = 512 Wh. On a warm day with 14 running hours, it is (60 × 14) + (2 × 10) = 860 Wh. A fixed 600 Wh daily allocation covers the first estimate and falls 260 Wh short of the second before delivery losses. These assumptions are not Dometic ratings.
Use A Full-Day Reading To Replace The Estimate
Use the existing monitor or manufacturer energy data for the mode you actually use. Note the starting cabinet temperature, door openings and daytime heat. A reading immediately after loading warm groceries includes pull-down work; one taken after midnight can miss it. If the fridge is already included in a whole-coach monitor total, keep it there or break it out once.
For an AC fridge add the inverter’s delivery losses and idle draw as appropriate. For a DC fridge use the losses of its actual supply path. Carry enough stored energy through the dark interval without counting sunshine before it reaches the panels. Keep normal food-storage checks independent of the energy estimate.